# Liquid-cooling coldplate

Canonical: https://semiaifoundry.com/learn/atlas/coldplate/
Revision: 2026-10-07
Rights: https://semiaifoundry.com/ai-atlas/licenses.html

Thermal path · Atlas v1.3.0

# Liquid-cooling coldplate

Captures heat at the processor and transfers it into flowing coolant.

[Explore in Atlas](https://semiaifoundry.com/ai-atlas/#coldplate)Centimeter-scale plate with submillimeter channel features; schematic geometry

Learning objectiveRelate coolant flow and heat capacity to temperature rise.

## The mechanism

A coldplate places a network of channels close to the heat source. Heat conducts through its metal base and enters coolant moving across the internal surfaces. Increasing contact area with small channels can improve heat transfer, but those channels also resist flow. The plate, pump, plumbing, coolant, and allowed temperatures therefore have to be designed together. Coolant travels from the inlet through channels near hot regions and leaves through the outlet, carrying the absorbed heat. Coolant temperature describes thermal energy transport; the flowing liquid is separate from the electrical power path. The warmed coolant still carries energy that must be transferred through the rack and facility cooling chain; the plate is only the point where that journey begins.

1.  Heat conducts from the package through the plate’s base into the internal channel surfaces.
2.  Coolant flowing over those surfaces absorbs thermal energy and warms as it crosses the plate.
3.  The outlet carries warmed coolant to the larger cooling loop, where energy is transferred onward and the fluid is conditioned for reuse.

## Science and assumptions

### Flow and temperature rise account for captured heat

$$
\dot Q=\dot m c_p(T_{\mathrm{out}}-T_{\mathrm{in}})
$$

Transported heat equals mass flow times specific heat times outlet-to-inlet temperature rise.

Symbols and units

Q̇

Heat transported by the coolant

W

ṁ

Coolant mass flow rate

kg/s

c\_p

Coolant specific heat capacity

J/(kg·K)

T\_out

Coolant outlet temperature

°C

T\_in

Coolant inlet temperature

°C

ṁ is coolant mass flow in kilograms per second and cp is specific heat capacity in J/(kg·K). Multiplying by the outlet-to-inlet temperature rise gives heat carried by the stream in watts. This measures transported energy, not the die temperature: the chip-to-fluid resistance still determines how hot the silicon must become to transfer that heat.

Assumptions Steady flow of a single-phase coolant with nearly constant heat capacity, negligible heat leakage, and no significant pressure-work or kinetic-energy change. Boiling and mixed-flow loops require a more general enthalpy balance.

## Engineering example

Removing 1 kW with water-like $c_{p}$ at 0.05 kg/s implies a temperature rise of roughly 4.8 K before plant losses.

## Distinctions and tradeoffs

Blue and red coolant in the atlas encode temperature, not electrical charge. The liquid transports heat; the chip receives power through a separate electrical path.

Smaller channels can improve heat transfer but increase pressure drop and pumping needs. Material compatibility, flow distribution, and reliable seals also shape the design.

Dense accelerators need continuous heat removal to sustain their operating limits. Liquid cooling makes higher rack compute density practical when the surrounding infrastructure supports it.

## Specifications and interfaces

Heat capture

Conduction followed by convection

Metal receives chip heat; fluid transports it away.

Useful balance

Q = mass flow × heat capacity × ΔT

Steady-state energy balance for the coolant stream.

Channel design

Microchannel arrays

CoolIT publishes split-flow examples; no exact GB200 channel geometry is asserted.

### Interfaces

Package heat Input

Thermal energy through contact interface

Coolant inlet Input

Conditioned fluid from server loop

Coolant outlet Output

Warmer fluid carrying captured heat

## Check your understanding

### Why can very small channels create a cooling tradeoff?

1.  They remove the need for a pump.
2.  They turn coolant into stored model weights.
3.  They can improve heat transfer while increasing resistance to fluid flow.

Answer and reasoning

They can improve heat transfer while increasing resistance to fluid flow.

More surface area can help heat exchange, but greater pressure drop raises pumping requirements and complicates flow distribution.

## Evidence and scope

Fluid properties, flow distribution and two-phase effects are omitted.

Vary total power and a lumped junction-to-coolant thermal resistance; local flow, spatial spreading and transients remain outside the model.

## Sources

-   [CoolIT: Split-Flow microchannel coldplate technology](https://www.coolitsystems.com/wp-content/uploads/2024/05/Split-Flow-Technology-CoolIT-Tech-Brief.pdf)
-   [CoolIT: The coldplate in a complete cooling system](https://www.coolitsystems.com/coldplate-technology/)

[Published lesson data](https://semiaifoundry.com/ai-atlas/lesson-data/coldplate-ee27baac4cdcf2f3.json) · [Atlas releases and licensing](https://semiaifoundry.com/ai-atlas/licenses.html)

## Continue exploring

### Foundations

-   [Thermal interface material](https://semiaifoundry.com/learn/atlas/thermal-interface/)
-   [Lid and heat spreader](https://semiaifoundry.com/learn/atlas/heat-spreader/)

### Related lessons

-   [GPU logic dies](https://semiaifoundry.com/learn/atlas/gpu-die/)
-   [Compute baseboard and tray](https://semiaifoundry.com/learn/atlas/compute-baseboard/)
-   [Coolant distribution unit and separated loops](https://semiaifoundry.com/learn/atlas/cdu/)